Various power supplies, industrial automation control, electric power systems, rectification systems, nuclear physics research and other industrial and scientific research technology fields.
Closed-loop Hall Current Sensors | |||||
Model number | Rated current | Output current | Accuracy | Supply voltage | Window dimensions |
IN(A) | IM(mA) | X(%) | Vc(V) | mm | |
CHB-2KB | 2000 | 400 | ±0.4% | ±24% | 105x105 |
CHB-3KB | 3000 | 600 | |||
CHB-4KB | 4000 | 800 | ±0.4% | ±24 | 105x105 |
CHB-5KB | 5000 | 1000 | |||
CHB-6KB | 6000 | 1200 | |||
parameters | |||||
Manufacturing principles | Hall magnetic compensation principle | ||||
Rated current | 2,000A…6,000A(DC、AC、Pulse current) | ||||
Output current ratio | 1:5000 The waveform of the output current on the secondary side is the same as that of the measured current on the primary side. | ||||
Measuring frequency | DC~20KHz | ||||
Response time | <1μS | ||||
Linearity | <0.1% | ||||
Supply voltage | ±24V(±5%) | ||||
Power consumption | 90mA+IM(Output current) | ||||
Insulation voltage | Between the primary and secondary circuits:6KV valid value/50Hz/1 minute | ||||
Operating temperature | -25℃~+70℃ | ||||
Installation method | Screw-fixed mounting | ||||
Application areas | Various power supplies, industrial automation control, electric power systems, rectification systems, nuclear physics research and other industrial and scientific research technology fields. |